How to use this calculator
Use the length convention and conductor units shown in the form, and select the relevant circuit arrangement. Compare the remaining voltage with the equipment’s operating requirements. This estimate does not replace conductor sizing for current capacity or applicable installation rules.
Examples
Custom 1.2 Ω/km wire
2 × 1 × 0.5 × 1.2 = 1.20 V, or 1.00%, leaving 118.8 V.Formula
DC and single phase: Vdrop = 2 × I × L × Z / parallel conductors.
Three phase: Vdrop = √3 × I × L × Z / parallel conductors.
For AC NEC data, effective impedance uses R × PF + X × √(1 − PF²).
Data and design limits
The 3% and 5% figures are design guidance reflected in NFPA's published NEC record, not a complete conductor-selection rule. The NEC-style mode uses tabulated resistance and reactance assumptions; the estimated-wire mode uses nominal resistance values; the custom mode is only as accurate as the entered impedance. None checks ampacity, temperature correction, bundling, terminal rating, fault-current duty, overcurrent protection, harmonics, or local amendments. Negative end voltage means the modeled conductor is plainly unsuitable, not that a physical circuit can deliver a negative terminal voltage.